 |
 |
 |
   |
 |
 |
            |
 |
|
Compressed air is often called the fourth utility (after water, electricity and gas) due to its widespread
use throughout industry. It is also the most expensive industrial utility, with about 10% of all electrical
energy used by industry employed in compressing air. By reviewing the compressed air system as a whole,
electricity consumption can be reduced and compression capacity increases avoided. This section discusses
how this can be achieved by repairing air leaks, reducing intake air temperature, optimising system pressure,
managing compressor operation and eliminating inappropriate uses of compressed air. It has often been found
that a plant with multiple compressors can operate with one less compressor when upgrades have been made.
Remember: to make effective improvements, a “systems approach” is crucial.
Taking Action
1.Are there leaks in the system?
> Info
|
|
 |
Stop your air leaks and save
25–40 % of your energy costs
|
|
|
|
It is likely that a typical plant that has not been
well maintained will have a leak rate of at least 20% of total
compressed air production capacity. By detecting leaks and
repairing them, air loss can be reduced to less than 10%.
Whilst the air compressor may be efficient, leaks in the
hoses, pipes, tools and joints can waste compressed air, and
hence electricity and money. Fixing leaks may be as simple as
tightening a connection or replacing faulty sections of
fittings.
As well as wasting energy, leaks cause a drop in system
pressure, which can cause equipment to operate less
efficiently.
> Action
|
|
Methods for finding leaks:
-
Shut off all equipment and start the compressor. Leaks can be found by listening for air escape sounds around
the plant. If there are no leaks, the compressor should not run at all once it has reached the specified pressure.
This test is best done on weekends or when the plant is not operational. You could also isolate one section of
the pipework at a time and monitor the rate of loss of compressed air. This allows you to locate the areas of greatest loss.
-
When your plant is idle and no compressed air-driven equipment is in use, monitor the energy use of your compressor.
Compare the energy consumption of the compressor during idle periods with that during operating periods to identify
the potential savings from cutting waste.
-
Establish a maintenance program using compressed air leak tags. These tags are simply placed on leaks as they are
identified by employees, making it easy for maintenance staff to locate the leaks.
-
Another effective way to detect leaks is to use an ultrasonic leak detector, which can be used without shutting off
equipment. These hand held detectors scan for leaks and through a headset, a leak can be heard, despite ambient noise.
Although they cost about $800 to buy, they often have a fast payback. For example, three 2mm holes leaking 15 litres/second
of compressed air increases annual energy consumption by around 10,000 kWh, costing $800 or more, so the cost of a meter
can be repaid by the savings realised by fixing just a few leaks. To hire a detector costs around $300/month. Look
under “Hire – electric and electronic test equipment” in the Yellow Pages for suppliers.
-
Use the Compressed Air calculator on the website tofind out how much air leaks are costing you.
2.Is there too much pressure?
> Info
In many industrial plants, air is supplied at a higher pressure
than is required. For example, some air compressors operate
in excess of 700kPa at full load. However, some types of
machinery and tools can operate efficiently at a lower air
pressure of 500–600kPa. This means the system is running
at an elevated pressure. The extra 100-200kPa includes a
contingency factor and compensates for possible leaks and
pressure drops across system. However, if your system is
well maintained, you can lower this operating pressure.
Pressure drops occur as the air travels from the compressor
through dryers, separators, filters and piping to the point of
use. This means that the pressure initially supplied by the
compressor is reduced at the end of the distribution system.
Unnecessary leaks and pressure drops create a situation
whereby supply pressure must be increased to compensate
for these losses. By ensuring that leaks and pressure drops
are minimised, the pressure can be properly matched to the
system demand without wasting energy and money.
Every 100 kPa reduction in operating pressure saves 8% on
energy costs.
|
|
 |
|
Implement a regular maintenance
program to identify and repair
compressed air leaks. Place
Compressed Air Leak Tags (see
sample) where leaks are found
and ensure the leaks are repaired
promptly.
Install compressor controls, such
as timers.
Consider replacing one large
compressor at part load with
several smaller ones operating at
full load.
|
|
|
>Action
- Determine if you have a pressure drop.
Pipes should be correctly sized for velocities of 6–10m/s. The
higher the velocity, the higher the pressure drop. Small pipe
sizes often result in high air velocities which cause excessive
pressure drop.
-
Find out the volume of air produced by your compressor (this
is written on the compressor).
-
Determine the cross sectional area of the pipe = (3.14) x
radius2.
-
Divide the volume by the area and then divide by 3600 (if not
already in volume of air per second) to
get velocity, i.e. velocity = volume of air per second/ cross
sectional area.
For example, if you have a compressor producing
air at 126L/sec (or 0.126 m3/sec) and a pipe leading directly
from the compressor which has a
50mm radius:
Area of pipe = 3.14 x (0.05)2 m2 = 0.00785.
The velocity is (0.126m3/0.00785m2) = 16m/s which is too
high and is causing drastic pressure drops. Therefore, take
the steps listed below to reduce your pressure drop.
-
Reduce pressure drops by fixing leaks, selecting components with the lowest possible pressure drop,
reducing the complexity of the distribution network (e.g. by minimising bends in the system) and
reducing the distance the air travels through the distribution system. Ideally, the pressure drop should
be no more than 10%. For example, if the air coming directly from the compressor is at 800kPa, and by the
end of the pipe it is 690kPa, the pressure drop is over 10% which means you are wasting energy and money.
-
Reducing system pressure means immediate
savings but requires careful matching of tools and air
compressor capacity.
-
If more pressure at point of use is needed, try to
reduce pressure drops and leaks before increasing
compressor pressure.
-
Remove unused compressed air lines and separate
unused equipment with a valve.
-
Consider dividing the distribution network into high
and low pressure sections to minimise unnecessary use of
high pressure. This is applicable when you:
-
have large quantities of air required at both low and high
pressure and need to use more than one compressor, or
-
have one specific machine that operates at a higher pressure
or is a long way from the compressors.
3.Is the temperature too high?
-
Energy savings can be made if the temperature of the
intake air is reduced. For every 3oC reduction in inlet
temperature, energy use is reduced by 1%. This can often be
achieved by ducting fresh air from outside (from a cool,
shaded area), generally with a payback period of 2-5 years.
4.What controls does the system have?
> Info
Since compressor systems are typically sized to
meet a system’s maximum demand, a control system is
almost always needed to reduce the output of
the compressor during times of lower demand.
Large energy savings can be made through accurate
matching of system supply and system demand.
A control system can shut off unneeded compressors and
turn on additional compressors when needed. Many
compressors have inbuilt controls to shut the compressor off
when not required. In a multi–
compressor situation, controls can chose the most efficient
compressor to use for any given demand.
>Action
-
Determine the type of control system needed
There are many types of controls. The one best
suited to your situation is determined by the number and type
of compressors being used and the
demand profile. It is important to seek advice from a
compressed air system control supplier.
-
Install a Variable Speed Drive (VSD)
A VSD allows the compressor to operate under a range of
loads by accurately matching the motor speed to the actual
load. This can help limit peak electricity demand by running
equipment for longer at a lower output. This is important
since peak demand charges can comprise 30% – 50% of
total
electricity costs.
Note: Some compressors run less efficiently at part load, so
seek expert advice. Also, you cannot retrofit a VSD to a
compressor, you must purchase a compressor already fitted
with a VSD.
This is applicable to most compressed air
systems and switches compressors off after production
periods.
5.What other options are there?
-
Compressed air is often used when other energy
sources are more economical.
-
One example is the use of a blower or fan for cooling, drying
and cleaning processes. This results in both energy and
dollar savings because the electric motors that run these
systems are much cheaper to operate than air compressor
motors. Modern electric hand tools (both plug-in and batterypowered)
have increasingly compact and powerful motors, so
they might sometimes replace compressed air powered
equipment.
-
Consider utilising the waste heat from your
compressors to pre-heat boiler feed water, process hot water,
or for other useful tasks. Up to 90% of the electricity used by
the compressor is converted to waste heat.
-
If you use compressed air to move particles or liquid,
consider installing a specially designed nozzle
which can be added onto the end of existing tubing. Such a
nozzle draws in surrounding air to increase
the volume of air and can reduce the amount of compressed
air needed for a task by 70%.
Calculate your savings
The Compressed Air Calculator calculates leak costs, pressure savings and temperature savings.
|
|